Performance Analysis of Multi-Machine System Using UPFC

Dr. P.R. Sharma, Dr. Rajesh Kr. Ahuja, Shakti Vashisth

In this paper best location of UPFC placement is identified on the basis of maximum loadability of a system. Simulation is done by using standard data of IEEE-14 bus system. Load reactance is increased by 5 %, 10 %, 15%, 20%, 25%, 30%, 35%, and 40%. Voltage stability index namely L-INDEX and FVSI is calculated at each percentage change in reactive load. Weakest line, the line at which voltage stability index has highest value and lower value of voltage, is measured using voltage stability index. UPFC is placed onthe most critical line which improves the voltage stability and minimizes the losses in the transmission system.

अस्वीकृति: इस सारांश का अनुवाद कृत्रिम बुद्धिमत्ता उपकरणों का उपयोग करके किया गया है और इसे अभी तक समीक्षा या सत्यापित नहीं किया गया है।

जर्नल हाइलाइट्स

अंकीय संकेत प्रक्रिया अतुल्यकालिक संकलन अधोचालकसंचालन अनुकूली संकेत संकेत अलग नेटवर्किंग आर्टिफ़िशियल क्लिनिक और इलेक्ट्रिकल में इलेक्ट्रिक ड्राइवर और उत्पाद इलेक्ट्रॉनिक सामग्री इलेक्ट्रॉनिक्स में आर्टिफिशियल ब्यूरो उपग्रह संचार एपीसैन निदान एवं संवेदन प्रणाली नियंत्रण सिद्धांत और सिद्धांत पावर इलेक्ट्रॉनिक कन्वर्टर्स का विश्लेषण बायो इलेक्ट्रॉनिक्स बिजली की गुणवत्ता और आपूर्ति की लागत के आर्थिक मूल्यांकन बेसिक इलेक्ट्रिकल इंजीनियरिंग भार एवं विद्युत पावर प्लांट की विद्युत एवं औषधि उपयोगिताएँ विद्युतचुंबकीय क्षणिक कार्यक्रम (ईएमआई) विद्युतीकरण